SciELO - Scientific Electronic Library Online

 
vol.20 número50Impacto de la penetración de la energía solar fotovoltaica en sistemas de distribución: estudio bajo supuestos del contexto colombianoEvaluación del desgaste por abrasión de una mezcla drenante modificada con residuo de llanta triturada (GCR) índice de autoresíndice de materiabúsqueda de artículos
Home Pagelista alfabética de revistas  

Servicios Personalizados

Revista

Articulo

Indicadores

Links relacionados

  • En proceso de indezaciónCitado por Google
  • No hay articulos similaresSimilares en SciELO
  • En proceso de indezaciónSimilares en Google

Compartir


Tecnura

versión impresa ISSN 0123-921X

Resumen

ALZATE GOMEZ, Alfonso; MURILLO YARCE, Duberney  y  SILVA CARDENAS, Ricardo León. Prototype for harmonic compensation in three phase systems. Tecnura [online]. 2016, vol.20, n.50, pp.96-105. ISSN 0123-921X.  https://doi.org/10.14483/udistrital.jour.tecnura.2016.4.a07.

ABSTRACT Context: The traditional methodology for the control of harmonics consists in the use of passive filters tuned to the harmonic components to be eliminated. Passive filters require a frequency-demanding design to avoid resonance phenomena with other elements and they not respond to changes in the dynamics of the electric power system. Method: A best-performing solution alternative is parallel power active filters. These filters, unlike passive filters, inject compensation currents into the network and have adaptation to changes in operating conditions. The implementation of an active filter involves hardware development but also software development. Algorithms are required for calculation of compensation currents and dc bus voltage control. Results: In this work a prototype for the harmonic compensation of 5kVA is designed and built in three phase distribution systems of 220V. The hardware fundamental elements are: coupling coil, capacitor, semiconductor devices and controller. The control algorithms that are responsible for the operation of the active filter at each instant of time are PQ theory, Linear Control-PWM and PI Control. Conclusions: The active power filters are a solution to the presence of harmonics in power systems. They compensate the harmonics generated by nonlinear loads and they don‘t have resonance problems and good dynamic response.

Palabras clave : Active filter; Current controller; Energy quality; Harmonics compensation; Power inverter.

        · resumen en Español     · texto en Español     · Español ( pdf )

 

Creative Commons License Todo el contenido de esta revista, excepto dónde está identificado, está bajo una Licencia Creative Commons